Quick find spares

Select industrie

Select brand

Select spare type

POL660 BURNER

Brand:NUWAY

The PO Series burner can operate on oil (Class D light oil, Class G HFO) and is available in standard outputs from 3.3MW to 18MW.

The P Series burner is commonly used on large industrial steam and hot water boilers.

SKU: PO660 Category:
Additional Information
Burner type

Oil Fired

Output

15500 – 18000

Series

Oil > POL Series

Technical data
Output: 15.5 - 18.0 MW Output
 Model PO660/17.2660/17.6660/18.0660/18.3660/18.7660/19.0660/19.4660/20.0
 Output (nett CV)MW15.515.916.216.516.917.117.518.0
 Fan SizekW4545555555555555
 Pump Motor  (Distillate Fuel)kW5.55.55.55.55.55.55.55.5
 Pump Motor  (Residual Fuel)kW5.55.55.55.55.55.55.55.5
 Pre-heater  (Residual Fuel only)kW5454545454545454
 Electrical SupplyV/Hz400/50400/50400/150400/50400/50400/50400/50400/50
 Oil inlet pressurepsi5 to 105 to 105 to 105 to 105 to 105 to 105 to 105 to 10
 Fuel pumpT5T5T5T5T5T5T5T5
 OperationFully ModulatingFully ModulatingFully ModulatingFully ModulatingFully ModulatingFully ModulatingFully ModulatingFully Modulating
 Control UnitAutoflame Mini Mk7Autoflame Mini Mk7Autoflame Mini Mk7Autoflame Mini Mk7Autoflame Mini Mk7Autoflame Mini Mk7Autoflame Mini Mk7Autoflame Mini Mk7
 Turndown up to 4:1up to 4:1up to 4:1up to 4:1up to 4:1up to 4:1up to 4:1up to 4:1
 Flame MonitorUV SensorUV SensorUV SensorUV SensorUV SensorUV SensorUV SensorUV Sensor
 Flame tube lengthsmm430/610430/610430/610430/610430/610430/610430/610430/610
 NoisedBA9393939393939393
 NOxmg/kWh140-190140-190140-190140-190140-190140-190140-190140-190
 COmg/kWh<100<100<100<100<100<100<100<100

Key Features:

• Available in monoblock design up to P310 or a duoblock design with a floor mounted combustion air fan
• Low NOx Head
• Electronic micro modulation air fuel ratio control with individual valve servo motors as standard
• Variable Speed Drive (VSD) combustion air fan motor
• Air inlet silencer (< 85dBA)
• Oxygen trim for improved efficiency and reduced emissions
• Separate or integrated water level controls for steam boilers
• Data Transfer Interface for BMS control

All P series burners are design and manufactured in accordance with EN267 and EN676.

Files & info

We help you to unlock & unleash the power within your Business…

×